Installation conductor
H03V-K, H05V-K, H07V-K
Copper conductor
PVC insulation
Application:
For wiring with small bending radii and higher requirements to the cable flexibility, in machines, devices, instruments and boards.
Technical characteristics:
- Produced according to DIN VDE 0281, part 3 / 12.95 (HD 21.3/95)
- Rated voltage:
- For H03V-K from 0.35 mm2: U0/U – 300/300 V
- For H05V-K from 0.50 mm2 to 1.00 mm2: U0/U – 300/500 V
- For H07V-K from 1.50 mm2 to 120 mm2: U0/U – 450/750 V
- Test Voltage:
- For H03V-K from 0.35 mm2: U0/U – 1500 V
- For H05V-K from 0.50 mm2 to 1.00 mm2: 2000 V
- For H07V-K from 1.50 mm2 to 120 mm2: 2500 V
- Insulation resistance at 70 0C: min. 1x1010 Ohm.cm
- Maximum conductor temperature: +70 °C
- Maximum conductor temperature at short circuit for 5 seconds: +160 °C
- Temperature Range: îò -30 °C äî +50 °C
- Minimum temperature during installation: -5 °C
- Minimum bending radius during installation:
- For diameters up to 10 mm - 10 D
- For diameters above 10 mm - 15 D
- Flame test: flame retardant according to IEC 60332-1
Cable Design:
- Flexible Copper conductors
- Flexibility class 5 according to DIN VDE 0295 (HD 383)
- Insulation: PVC
Colour coding:
- White, Gray, Black, Blue, Brown, Violet, Orange, Pink, Turquoise, Red, Green, Yellow
A double-coloured insulation as a combination of above indicated colours is permissible.
Data:
Nominal Section, mm2 |
Nominal Cable Diameter, mm |
Nominal Copper Weight, kg/km |
Nominal Cable Weight, kg/km |
0.35 |
1.8 |
3.36 |
6 |
0.5 |
2.2 |
4.8 |
10 |
0.75 |
2.4 |
7.2 |
13 |
1 |
2.6 |
9.6 |
15 |
1.5 |
3.0 |
14.4 |
22 |
2.5 |
3.7 |
24.0 |
35 |
4 |
4.2 |
38.4 |
50 |
6 |
4.8 |
57.6 |
71 |
10 |
7.0 |
96.0 |
127 |
16 |
7.8 |
153.6 |
187 |
25 |
9.7 |
240.0 |
288 |
35 |
10.9 |
336.0 |
384 |
50 |
13.7 |
480.0 |
560 |
70 |
16.1 |
672.0 |
783 |
95 |
17.3 |
912.0 |
1006 |
120 |
19.3 |
1152.0 |
1287 |
Please contact us for more information.
|
|