Installation conductor

H07V-R
Copper conductor PVC insulation



Application:

For fixed installation in lighting networks, power and signal systems, wiring in control boards, machines and instruments.

Technical characteristics:

  • Produced according to DIN VDE 0281, part 3
  • Rated voltage: U0/U – 450/750 V
  • Test Voltage: 2500 V
  • Maximum conductor temperature: +70 °C
  • Maximum conductor temperature at short circuit for 5 seconds: +160 °C
  • Temperature Range: îò -30 °C äî +50 °C
  • Minimum temperature during installation: -5 °C
  • Minimum bending radius during installation:
    • For diameters up to 10 mm - 10 D
    • For diameters above 10 mm - 15 D
    D - conductor diameter
  • Flame test: flame retardant according to IEC 60332-1
Cable Design:
  • Flexible Copper conductors
  • Flexibility class 2 according to DIN VDE 0295 (HD 383)
  • Insulation: PVC
Colour coding:

  • Yellow-green, White, Black, Gray, Blue, Brown, Red

Data:

Nominal Section, mm2 Nominal Conductor Diameter, mm Nominal Copper Weight, kg/km Nominal Conductor Weight, kg/km
1.5 3.0 14.4 24
2.5 3.7 24.0 36
4 4.3 38.4 55
6 4.9 57.6 75
10 6.2 96.0 125
16 7.3 153.6 189
25 9.0 240.0 295
35 10.2 336.0 393
50 12.0 480.0 528
70 13.8 672.0 754
95 16.1 912.0 1030